Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

35

• In-suite signal silence applies only to output devices and NACs that are

configured as silenceable. It cannot be used in local alarm signaling

applications.

• You cannot use a delay timer with in-suite correlation groups.
• No special hardware is required.
• In-suite signal silence is required by Ontario Building Code 3.2.4. For

instructions on programming in-suite signal silence in a typical system, see

“Adding and removing panel events” on page 90

Programming modes

You can choose from three levels of program automation: Auto programming,

incremental programming, or advanced programming. These are discussed in

the following sections.

Auto programming

The Auto Program command is used to automatically configure the control panel

and remote annunciators from their respective front panels.
Auto programming replaces the existing project database with a default project

database based on the hardware configuration that it detects. The default project

database configures the system as a general fire alarm system that activates all

notification appliance circuits when any fire alarm input is activated.
Auto programming can also be used as a first step, to be followed by some

advanced programming to customize individual settings. The Auto Program

command lets you choose:
• Automatic zone assignments

• The event notification level to use

• Manual or automatic device and zone labeling during auto programming

• The “base follow” option for relay and sounder bases

• CMS network and dialer options

Note:

Auto programming does not overwrite the previous CMS programming.

However, the restore panel defaults option in the program menu does change the

CMS configuration.
To auto program a panel, see “Auto programming the panel” on page 61

Incremental programming

The Incremental Program command is used to make changes to a panel that has

already been programmed. Incremental programming lets you add and label

devices and zones in the existing database without affecting any other settings.