Restarting the panel

The Panel Restart command restarts (reboots) the panel without having to cycle

AC power.

To restart the panel:

1. Press the menu button and choose Program.
2. Choose Panel Restart.
3. Enter your level two password (or greater).
4. Choose Yes to restart the panel.

— or —
Choose No to cancel.

Main Menu

Reports

Test

Control

Program

Program

Laptop Enable

Programmable Keys

Panel Restart

Enter Password

0000

Panel Restart

Yes

No

Enabling RS232 communication

The RS232 CU Enable command lets you connect a PC to the control panel by

means of the optional RS-232 card. This enables you to use the Configuration

Utility (CU) to program the panel and upload or download panel data.

Note:

The RS232 CU Enable command times out (turns off) after four minutes of

inactivity, meaning that if communication is enabled but the panel does not

connect to the CU PC within four minutes, communication is automatically

disabled.

To enable RS-232 communication:

1. If you are using a printer, disconnect the printer

cable from the RS-232 card.

2. Connect the configuration utility computer to the

RS-232 card.

3. Press the Menu button and choose Program.
4. Choose RS232 CU Enable.

Main Menu

Reports

Test

Control

Program

Program