Chapter 2: Front panel programming

130

E-FSA64 and E-FSA250 Technical Reference Manual

To program panel events:

1. Press the Menu button and choose Program.
2. Choose Advanced Program.
3. Enter a level two password.
4. Choose Panel Events.
5. Select the event to be programmed.
6. Choose Event Notification.
7. Configure the event notification options. See the

default settings in the table above. Not all options

shown here are displayed on all systems.
Printer: Yes or No. This controls whether event

information is sent to the printer
Dialer:
• Acct 1 2: Event information is sent to both

dialer accounts

• Acct 1: Event information is sent to dialer

account one

• Acct 2: Event information is sent to dialer

account two

• None: Event information is not sent to the

dialer

CID: Contact ID event code (000 to 999)
Network: Controls whether event information is

sent to the connected network

8. When you have finished configuring each page,

choose Save.

9. Repeat steps 6 to 9 for each panel event.
10. Press the Menu button to exit menu mode, or

continue programming.

Main Menu

Reports

Test

Control

Program

Program

Auto Program

Advanced Program

Date and Time

Enter Password

0000

Advanced Program

Panel Operation

Panel Events

Loop Events

Panel Events

System Startup

Ground Fault

Battery Charger

System Startup

Event Notification

Active

Printer Yes<>

Dialer Account 1&2

CID 110

Network Yes<>

Network

Network 01 >

Network 02

Network 03

Network 01

Enabled Yes<>

Save

Loop event programming

Loop events, such as loop fault, map fault, and loop initialization have an event

notification setting for contact ID, dialer, NET (1-8), and printer, which controls

where the event is sent when it takes place. Each event has a factory default

setting that can be used with no additional programming.