UL 864 programming requirements

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER

INVOLVED PARTIES

This product incorporates field-programmable software. In order for the product to comply with

the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL

864, certain programming features or options must be limited to specific values or not used at

all as indicated below.

Programmable

feature or option

Permitted in

UL 864 (Y/N)

Possible

settings

Settings

permitted in UL

864

Panel default

AC fail delay

Y

0 to 15 hours

1 to 3 hours

3 hours

Telephone line cut

supervision

duration

Y

1 to 120 seconds 10 to 120

seconds

120 seconds

Telephone line

ground fault

Y

Disabled

Enabled

Enabled

Enabled

Transmission test

frequency

Y

0 to 45 days

1 (daily)

1 (daily)

Dialer mode

Y

Dual line

Single line

Modem only

None

Dual line

Single line [2]

Modem only [3]

None [3]

Dual line

Dialer retries

Y

5 to 10

5 minimum

5 retries

Dialer retry time

Y

1 to 45 seconds Yes

5 seconds

Send event restore

codes

Y

No

Yes

Yes

Yes

Swinger shutdown N

Off

1 to 255

Off

Off

Zone resound

Y

On

Off

On

On

[1] Allowed only if the IDC is connected to the latching alarm device
[2] Allowed only when the supervising station supervises the telephone line and annunciates

fault conditions within 200 seconds

[3] Prohibited when the control panel is connected to a supervising station