Central monitoring station device programming – Edwards Signaling eFSA250 User Manual
Page 127
Chapter 2: Front panel programming
E-FSA64 and E-FSA250 Technical Reference Manual
115
To program an annunciator:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2
password.
3. Choose Panel Configuration.
4. Choose Annunciator.
5. Choose the annunciator you want to program.
6. Program each annunciator in the system using
Table 31 on page 114.
7. When you finish programming each option,
choose Save.
8. Press the Menu button to exit menu mode, or
continue programming.
Panel Configuration
Panel NAC
Ann. Class A<>
Annunciator
Annunciator
Annunciator 01
Annunciator 02
Annunciator 03
Annunciator 01
Type Off<>
Expanders 1
Label >
Annunciator 01
Label >
Event Notification
Save
Central monitoring station device programming
CMS device programming
CMS devices are the devices that transmit system events to a central monitoring
station’s receiver. This includes the dialer and the network.
Table 32: CMS device options
Option
Description
Dialer
See “Dialer programming” on page 117.
Network
See “CMS network (transmitter) programming” on page 120.
Swinger shutdown
Set swinger shutdown to Off or 1 to 255 repetitions. When you
have finished, press Enter to save.
Note:
Off is the only acceptable setting for UL/ULC installations.
See “UL 864 programming requirements” on page 31 for details.
This automatically inhibits the number of consecutive times a
single trouble event is transmitted over a 24-hour period before
it is no longer sent. Some trouble events are not affected when
swinger shutdown is set. They are: