Central monitoring station device programming – Edwards Signaling eFSA250 User Manual

Page 127

Advertising
background image

Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

115

To program an annunciator:

1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2

password.

3. Choose Panel Configuration.
4. Choose Annunciator.
5. Choose the annunciator you want to program.
6. Program each annunciator in the system using

Table 31 on page 114.

7. When you finish programming each option,

choose Save.

8. Press the Menu button to exit menu mode, or

continue programming.

Panel Configuration

Panel NAC

Ann. Class A<>

Annunciator

Annunciator

Annunciator 01

Annunciator 02

Annunciator 03

Annunciator 01

Type Off<>

Expanders 1

Label >

Annunciator 01

Label >

Event Notification

Save

Central monitoring station device programming

CMS device programming

CMS devices are the devices that transmit system events to a central monitoring

station’s receiver. This includes the dialer and the network.

Table 32: CMS device options
Option

Description

Dialer

See “Dialer programming” on page 117.

Network

See “CMS network (transmitter) programming” on page 120.

Swinger shutdown

Set swinger shutdown to Off or 1 to 255 repetitions. When you

have finished, press Enter to save.

Note:

Off is the only acceptable setting for UL/ULC installations.

See “UL 864 programming requirements” on page 31 for details.
This automatically inhibits the number of consecutive times a

single trouble event is transmitted over a 24-hour period before

it is no longer sent. Some trouble events are not affected when

swinger shutdown is set. They are: