• If you choose to label devices during auto programming, devices are labeled
by entering the address of the device and then entering the label for the
device. It is important for you to have the Device Settings worksheet filled out
for each device so that you can easily select a device ID and label it correctly.
Auto programming options
Table 20 below describes the options to be set when auto programming the
panel.
Table 20: Auto programming options [1]
Option
Description
Auto zoning
This option controls whether devices are automatically assigned to zones.
The number of devices assigned to a zone is based on the type of panel:
• eFSA64 panel: Four devices per zone
• eFSA250 panel: Eight devices per zone
Yes: The system automatically finds all of the devices connected to the
system and assigns them to a zone. Only the primary element of dual
element detectors are assigned to a zone.
No: The system automatically finds all of the devices connected to the
system and does not assign them to a zone.
Enable NET
Configures the panel to communicate with a central monitoring station
(CMS) via an Ethernet network.
Yes: Enables Ethernet communication with the central monitoring station
(CMS).
No: Disables Ethernet communication with the CMS.
Dialer
Configures the panel to communicate with the CMS via a dialer. The
dialer is configured as a dual line so that all messages are sent to two
separate receivers with different phone numbers and account codes.
Note:
Not all dialer programming options are acceptable for UL/ULC
installations. See “UL 864 programming requirements” on page 31 for
details.
Yes: Enables the dialer and configures it for dual-line communication with
the CMS. All messages will be sent to two separate receivers that have
different phone numbers and account codes.
No: Dialer is not enabled.