Introduction, What you’ll need – Edwards Signaling eFSA250 User Manual

Page 227

Advertising
background image

Appendix B: Worksheets

E-FSA64 and E-FSA250 Technical Reference Manual

215

Notification appliance circuit calculations

worksheet

Introduction

This topic shows you how to determine the maximum cable length of a

notification appliance circuit (NAC) for a given number of appliances.
Two methods are presented: worksheet and equation. The worksheet method is

simpler, but your installation must meet the criteria listed on the worksheet. If

your installation does not meet these criteria, you need to use the equation

method.
The methods given here determine cable lengths that work under all operating

conditions. The calculations ensure that the required operating voltage and

current are supplied to all notification appliances. To do this, we assume these

two worst-case conditions:
• The voltage at the NAC terminals is the minimum provided by the power

supply

• The notification appliances are clustered at the end of the NAC cable
Other, more detailed methods that distribute the appliance load along the NAC

cable may indicate that longer cable runs are possible.

What you’ll need

Appliance and cable values

Whether you use the worksheet method or the equation method, you’ll need to

know:
• The minimum operating voltage required for the appliances

• The maximum operating current drawn by each appliance

• The resistance per unit length of the wire used (Ω/ft.)
This information can be found on the appliance installation sheets and on the

cable specification sheet.

Power supply values

For either method, you’ll need some fixed or calculated operating values for your

specific power supply. The fixed values are:
• Source voltage = 20.4 V

• Load factor for eFSA64 panel = 0.20 V/A

Advertising
This manual is related to the following products: