Appendix D: Applications

E-FSA64 and E-FSA250 Technical Reference Manual

265

Message Line 1: 24VDC_RISER
Message Line 2: SOUNDER_RLY_1

5. Configure Correlation 001 as follows:

Add/Remove Device: All alarm signal-initiating devices
Add/Remove NAC: All RLY modules used to active sounder bases

In-suite signal silence applications

This section provides high level instructions for creating an in-suite signal silence

application based on the use of correlation groups. Additional background

material and detailed instructions are also available. See:
• “What is in-suite signal silence?” on page 34
• “Programming in-suite signal silence” on page 92
• “What is a correlation group?” on page 32
• “Correlation group programming” on page 86

Figure 60: Building with a separate audible circuit for each floor and separate circuits for

audibles within and not within dwelling units

NAC 1

NAC 2

NAC 8
NAC 7

NAC 9

NAC 10

NAC 6
NAC 5

NAC 4
NAC 3

Floor 5

Floor 4

Floor 3

Floor 2

Floor 1

Rooms

Hallways