Correlation group programming – Edwards Signaling eFSA250 User Manual
Page 98
Chapter 2: Front panel programming
86
E-FSA64 and E-FSA250 Technical Reference Manual
To change loop configuration options:
1. Press the menu button and choose Program.
2. Choose Advanced Program.
3. Enter a level two password.
4. Choose Loop Configuration.
5. Program the options.
Main Menu
Reports
Test
Control
Program
Program
Incremental Program
Auto Program
Advanced Program
Enter Password
0000
Advanced Program
Loop Configuration
Panel Configuration
Panel Operation
Correlation group programming
This section includes instructions for:
• Using fast groups
• Adding members to correlation groups
• Enabling in-suite signal silence
• Setting the activation count
• Copying members of a correlation group
• Removing all members from a correlation group
Note:
To meet the UL\ULC requirement that evacuation signals activate within
10 seconds, assign sounder base detectors to “fast” correlation groups.
See “Programming fast groups for sounder bases” on page 93.
If you are new to correlation group programming, see “What is a zone?” on page
32.
Adding members to correlation groups
Correlation groups can include zones, NACs, devices, unconfigured alarm
events, and the common trouble event. See the following procedure.