Chapter 2: Front panel programming

86

E-FSA64 and E-FSA250 Technical Reference Manual

To change loop configuration options:

1. Press the menu button and choose Program.
2. Choose Advanced Program.
3. Enter a level two password.
4. Choose Loop Configuration.
5. Program the options.

Main Menu

Reports

Test

Control

Program

Program

Incremental Program

Auto Program

Advanced Program

Enter Password

0000

Advanced Program

Loop Configuration

Panel Configuration

Panel Operation

Correlation group programming

This section includes instructions for:
• Using fast groups

• Adding members to correlation groups

• Enabling in-suite signal silence

• Setting the activation count

• Copying members of a correlation group

• Removing all members from a correlation group

Note:

To meet the UL\ULC requirement that evacuation signals activate within

10 seconds, assign sounder base detectors to “fast” correlation groups.
See “Programming fast groups for sounder bases” on page 93.
If you are new to correlation group programming, see “What is a zone?” on page

32.

Adding members to correlation groups

Correlation groups can include zones, NACs, devices, unconfigured alarm

events, and the common trouble event. See the following procedure.