Chapter 2: Front panel programming

82

E-FSA64 and E-FSA250 Technical Reference Manual

Adding devices

To add a device to a programmed system:

1. Install the device on the system.

The system recognizes the new device and

displays a trouble event message that indicates

that there is an unprogrammed device.

2. Press Enter.

The device details screen is displayed.

3. Press Enter again, and enter a level two password

(if you are not already logged on).
The Add Device screen is displayed.

4. Verify the device that you are about to add, and

press Enter.
The Device programming menu displays. If the

device is not a valid device, “invalid device”

displays and you will be unable to program the

device.

5. Program device options using Table 22 on page

66.
Some device options have a factory default setting

that you can accept or change. See “Factory

default settings” on page 36.
If you added a dual address device, both

addresses for the device are displayed on the

screen (e.g. 001/002). The first address listed is

the device address you are programming. When

you pick the second address to program, both

addresses are still displayed but in reverse order

(e.g. 002/001).
Depending on the type of device you are

programming, some of the options in the Table 22

on page 66 may not be available.

6. When you have finished programming each

option, choose Save. The device is added to the

database and the unprogrammed device event is

cleared.

00:00:00 A001 D001

001 Trouble

Unconfigured Trouble

Loop x Device xxx

Device type

Enter Password

0000

Add Loop x

Device 001

Device label

<-Continue <Back

Device 001

Zone 01<>

Label >

Correlation Groups

Device 001

Base Follow Device<>

Type Smoke<>

Save