Adding devices – Edwards Signaling eFSA250 User Manual
Page 94
Chapter 2: Front panel programming
82
E-FSA64 and E-FSA250 Technical Reference Manual
Adding devices
To add a device to a programmed system:
1. Install the device on the system.
The system recognizes the new device and
displays a trouble event message that indicates
that there is an unprogrammed device.
2. Press Enter.
The device details screen is displayed.
3. Press Enter again, and enter a level two password
(if you are not already logged on).
The Add Device screen is displayed.
4. Verify the device that you are about to add, and
press Enter.
The Device programming menu displays. If the
device is not a valid device, “invalid device”
displays and you will be unable to program the
device.
5. Program device options using Table 22 on page
66.
Some device options have a factory default setting
that you can accept or change. See “Factory
default settings” on page 36.
If you added a dual address device, both
addresses for the device are displayed on the
screen (e.g. 001/002). The first address listed is
the device address you are programming. When
you pick the second address to program, both
addresses are still displayed but in reverse order
(e.g. 002/001).
Depending on the type of device you are
programming, some of the options in the Table 22
on page 66 may not be available.
6. When you have finished programming each
option, choose Save. The device is added to the
database and the unprogrammed device event is
cleared.
00:00:00 A001 D001
001 Trouble
Unconfigured Trouble
Loop x Device xxx
Device type
Enter Password
0000
Add Loop x
Device 001
Device label
<-Continue <Back
Device 001
Zone 01<>
Label >
Correlation Groups
Device 001
Base Follow Device<>
Type Smoke<>
Save