Chapter 1: Installation and wiring

26

E-FSA64 and E-FSA250 Technical Reference Manual

Requirements

When connecting a CTM to the panel, the following hardware and programming

requirements must be met:
• The CTM must be connected to either a panel NAC, or a NAC module
• The NAC used must be dedicated to CTM use only
• All alarm points or zones (if programmed as a zoned system) must be

programmed to activate the dedicated NAC

• The NAC used must be programmed as City Tie

Wiring

The following wiring diagrams show how the polarity switches during an alarm

condition.

Figure 37: CTM module wiring (panel in normal condition)

Notification

appliance circuit

1

1

2

2

CTM

+

+

+

+

_

_

_

_

[1] [2]

Master box

Normal condition

[3]

[4]

[5]

[6]

Public fire alarm

reporting system

3

4

Figure 38: CTM module wiring (panel in alarm condition)

Notification

appliance circuit

1

1

2

2

CTM

+

+

+

+

_

_

_

_

[1] [2]

Master box

Public fire alarm

reporting system

Alarm condition

[3]

[4]

[5]

[6]

3

4

[1] 200 mA into a 14.5 Ω trip coil max. loop

resistance = 25 Ω

[2] This circuit is nonpower-limited and is

supervised for grounds and opens, but

not shorts

[3] Supervised and power-limited

[4] NAC must be programmed for city tie
[5] CTM must be mounted in the same room

as the panel

[6] 15 kΩ end-of-line resistor