Edwards Signaling eFSA250 User Manual

Page 138

Advertising
background image

Chapter 2: Front panel programming

126

E-FSA64 and E-FSA250 Technical Reference Manual

Option

Description

Zone resound

Set zone resound to:
On: NACs resound each time a device in the zone goes into

alarm even if they were silenced.
Off: Inhibits the NACs from turning on again (after they were

silenced) when a second device in the zone goes into alarm.

The “off” setting is not acceptable for UL/ULC installations. See

“UL 864 programming requirements” for details.

Reset inhibit

Set the time to:
Off: Panel reset is operational immediately after NACs turn on.
1 minute: Panel reset is operational one minute after NACs turn

on.

Auto signal silence

Set auto signal silence to:
Off: Does not allow the panel to automatically silence the

signals.
5 to 30 minutes: Allows the panel to automatically silence the

signals after the selected time period expires.

Suite signal silence

Set the timer duration. The range of possible values is 1 to 10

minutes. The default value is 10 minutes.

Daytime start

Set the start time for daytime sensitivity.

Nightime start

Set the start time for nighttime sensitivity.

Date

Set the date format to:
U.S.: MM/DD/YYYY
Canada: DD/MM/YYYY

LCD banner

Enter the desired banner text for line one and line two using the

keypad. Each line can have up to 20 characters. When you

have finished, choose Save. The LCD banner does not display

when the panel is in any off-normal state.

Aux power reset

On: “Reset” temporarily turns off the resettable aux power

output. This is required when the output is used for powering

four-wire smoke or four-wire duct smoke detectors.
Off: “Reset” does not turn off the resettable aux power output.

This is required when the output is used to power remote

annunciators.

Event notification

Set event notification to:
Zone: When a device is a member of a zone, only the zone

information is sent to the LCD, LEDs, printer, and dialer. Note,

device level reporting configuration is not available.
Zone/device: Zone information is sent to the LCD and LEDs.

Device information is sent to the printer and dialer. Zone/device

reporting locations can be configured through custom

Advertising
This manual is related to the following products: