Edwards Signaling eFSA250 User Manual
Page 49
Chapter 2: Front panel programming
E-FSA64 and E-FSA250 Technical Reference Manual
37
Note:
Depending on panel equipment and programming, some of these settings
may not be available.
Default passwords
The panel comes standard with a set of default passwords. These are:
• Level 1: 1111
• Level 2: 2222
• Remote annunciator: 3333
Note:
We recommend that you change the default passwords after programming
the system.
Default panel operation settings
• Language: English
• Marketplace: US
• AC fail delay: 3 hours
• Zone resound: On
• Reset inhibit: Off
• Auto signal silence: Off
• Suite signal silence: 10 minutes
• Day start: 06:00
• Night start: 18:00
• Date format U.S.: MM/DD/YYYY
• Aux power reset: On
• LCD banner: Blank
• Event notification: Device
• Key #1: NONE
• Key #2: NONE
Other default panel settings
• Daylight saving
Enabled: No
Month start: 03
Month end: 11
Week start: 1
Week end: 0
Weekday start: 0
Weekday end: 0
Hour start: 02
Hour end: 02
Offset minutes: 60
• RS232 CU Enable: Off
• Lock remote read: No
Default panel configuration settings
• IP: 192.168.001.003
• Subnet mask: 255.255.255.0
• Gateway: 000.000.000.000
• Panel NACs
Class: Class B
Type: Continuous silenceable
Correlation group: 1