Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

37

Note:

Depending on panel equipment and programming, some of these settings

may not be available.

Default passwords

The panel comes standard with a set of default passwords. These are:
• Level 1: 1111

• Level 2: 2222

• Remote annunciator: 3333

Note:

We recommend that you change the default passwords after programming

the system.

Default panel operation settings

• Language: English
• Marketplace: US
• AC fail delay: 3 hours
• Zone resound: On
• Reset inhibit: Off
• Auto signal silence: Off
• Suite signal silence: 10 minutes
• Day start: 06:00

• Night start: 18:00

• Date format U.S.: MM/DD/YYYY
• Aux power reset: On
• LCD banner: Blank
• Event notification: Device
• Key #1: NONE
• Key #2: NONE

Other default panel settings

• Daylight saving

Enabled: No

Month start: 03

Month end: 11

Week start: 1

Week end: 0

Weekday start: 0

Weekday end: 0

Hour start: 02

Hour end: 02

Offset minutes: 60

• RS232 CU Enable: Off
• Lock remote read: No

Default panel configuration settings

• IP: 192.168.001.003
• Subnet mask: 255.255.255.0
• Gateway: 000.000.000.000
• Panel NACs

Class: Class B

Type: Continuous silenceable

Correlation group: 1