DIP Switches of Analog Output Models

1402-027

Figure 6

DIP Switch Settings of Analog Output Models

DIP Position

Setting

1

Non-metric Non-metric units (°F).

Metric

Metric units (°C).

2

Td

Td (dewpoint) as humidity parameter on display and

analog output. Sets analog output scaling

to -20 ... +55 °C.

RH

RH (relative humidity) as humidity parameter on display

and analog output. Sets analog output scaling to

0 ... 100 %RH.

3

0...5V or

0...20 mA

Set analog output channels to 0 ... 5 V (voltage output) or

0 ... 20 mA (current output)

0...10V or

4...20 mA

Set analog output channels to 0 ... 10 V (voltage output)

or 4 ... 20 mA (current output)

4

Not used

5

Not used

6

Not used

7

Not used

8

Custom

Configuration through service port only.

DIP

Configuration by DIP switches only.

Resets display analog outputs to standard settings.

NOTE

If DIP switch 8 is set to Custom, the transmitter ignores all other DIP

switch settings. In custom mode the transmitter uses settings that are

configured in software using the service port. Before changing the

position of this switch, see section Changing Between DIP and Custom

Configuration on page 21.