Carbon dioxide object, Table 19 carbon dioxide object properties, Table 20 status flags – Vaisala GMW90 User Manual

Page 90: Table 21 reliability, Table 22 event state

Advertising
background image

User's Guide _______________________________________________________________________

88 ___________________________________________________________________ M211659EN-B

Carbon Dioxide Object

Table 19

Carbon Dioxide Object Properties

Property

Data type

(Application Type)

Writable

(Conformance Code)

Value or Initial Value Persistence

Object_Identifier BACnetObjectIdentifier

No (R)

00 00 00 01 (hex)

Object Type = 0,

Instance = 1

Nonvolatile

Object_Name

CharacterString

No (R)

"CO2"

Nonvolatile

Object_Type

BACnetObjectType

(ENUMERATED)

No (R)

0 (Analog Input)

Fixed

Present_Value

Real

Yes

(When Oos) (R)

0.0

Volatile

Description

CharacterString

No (O)

"Carbon Dioxide"

Nonvolatile

Units

BACnetEngineeringUnits

(ENUMERATED)

No (R)

96 (parts-per-million)

Nonvolatile

Status_Flags

BACnet Status Flags

(BIT STRING)

Yes (when OoS) (R)

0 (FAULT == FALSE) Volatile

Reliability

BACnet Reliability

(ENUMERATED)

Yes (when OoS) (O)

0 (NO FAULT

DETECTED)

Volatile

Event State

BACnetEventState

(ENUMERATED)

No (R)

0 (NORMAL)

Volatile

Out_of_Service

BOOLEAN

Yes (R)

0 (FALSE)

Volatile

COV_Increment

Real

Yes (O)

NaN (COV reporting

disabled)

Nonvolatile

Min_Pres_Value Real

No (O)

0.0 (same as limit for

UNDER_RANGE)

Nonvolatile

Max_Pres_Value Real

No (O)

2400 (same as limit for

OVER_RANGE)

Nonvolatile

Table 20

Status Flags

Flag

State

Cause

IN_ALARM

FALSE

Event State equals 0 (NORMAL)

TRUE

Event State not 0

FAULT

FALSE

Reliability equals 0 (NO FAULT DETECTED)

TRUE

Reliability not 0

OVERRIDDEN

FALSE

Always FALSE

OUT_OF_SERVICE

FALSE

Present Value may NOT be written via BACnet

TRUE

Present Value may be written via BACnet

1)

Table 21

Reliability

State

Cause

0 NO_FAULT_DETECTED

1 NO_SENSOR

No contact to measurement module

2 OVER_RANGE

CO2 level over BAC_CO2_MAX_VALUE

3 UNDER_RANGE

CO2 level under BAC_CO2_MIN_VALUE

7 UNRELIABLE_OTHER

Other measurement error

Table 22

Event State

State

Cause

0 NORMAL

Reliability equals 0 (NO FAULT DETECTED)

1 FAULT

Reliability not 0

Advertising