Chapter 5 _______________________________________________________________ Maintenance

VAISALA ________________________________________________________________________ 67

Adjustment Using a Hand-Held Meter

GMW90 transmitters can be adjusted using Vaisala hand-held meters

HM70 (for humidity and temperature) and GM70 (for carbon dioxide and

temperature).

1.

Connect the GMW90 series transmitter to the MI70 indicator using

the connection cable (Vaisala order code 219980). MI70 indicator

is the hand-held display device that is included with HM70 and

GM70.

2.

Depending on the connected devices, you may be prompted to

check the currently applied environment settings. Check the

settings when prompted.

3.

In the Functions menu of the MI70 indicator, select Calibrate

XMW9x and press Start.

4.

Confirm Yes. Confirm the automatic power off notification with

Ok.

5.

Select parameter for adjustment: CO

2

, RH, or T.

6.

Screen shows the measured values and their difference. Press

Adjust to select the Adjustment mode.

7.

Select the desired adjustment type using arrow buttons and press

Select:
- To same as reference: Adjusts the measurement of the GMW90

transmitter to the same reading as the reference that is connected

to the other port of the MI70 indicator. This option is not

available if no reference for the selected parameter is connected

to the MI70 indicator.

- 1-point adjustment: Adjusts the measurement of the GMW90

to a reference value that you specify. Follow the instructions

from the MI70 indicator when using this option.

- 2-point adjustment: Adjusts the measurement of the GMW90

at two points to reference values that you specify. This option is

not available when adjusting temperature (T).

- Revert factory calib.: This option removes the currently

applied user adjustment from the measurement module (GM10

module for CO

2

, HTM10 module for RH or T). Only the

adjustment for the selected parameter is removed.

8.

Complete the selected adjustment by following the instructions

from the MI70 indicator.