Modbus reference, Appendix b – Vaisala GMW90 User Manual

Page 98

Advertising
background image

User's Guide _______________________________________________________________________

96 ___________________________________________________________________ M211659EN-B

APPENDIX B

MODBUS REFERENCE

This appendix describes the Modbus protocol implementation of the

GMW90 series digital transmitters.

NOTE

For more information on Modbus protocol, refer to the Specification and

Implementation Guide for Modbus Over Serial Line.

NOTE

Serial line settings such as baud rate are configured using DIP switches.

See section Configuration of Digital Output Models on page 21.

Table 42

Modbus Functions Supported by GMW90

Function Code

Name

03 (0x03)

Read Holding Registers

04 (0x04)

Read Input Register

06 (0x06)

Write Single Register

16 (0x10)

Write Multiple Registers

43 / 14 (0x2B / 0x0E)

Read Device Identification

Table 43

GMW90 Modbus Measurement Data Registers

Name Metric float Metric

integer

Metric

unit

Non-metric

float

Non-metric

integer

Non-metric

unit

CO2 0001…0002 0257 (×1)

ppm

6401…6402 6657 (×1)

ppm

RH

0003…0004 0258 (×0.01) %RH 6403…0004 6458 (×0.01) %RH

T

0005…0006 0259 (×0.01) °C

6405…0006 6459 (×0.01) °F

Td

0007…0008 0260 (×0.01) °C

6407…0008 6460 (×0.01) °F

Tdf

0009…0010 0261 (×0.01) °C

6409…0010 6461 (×0.01) °F

dTd

0011…0012 0262 (×0.01) °C

6411…0012 6462 (×0.01) °F

Tw

0013…0014 0263 (×0.01) °C

6413…0014 6463 (×0.01) °F

a

0015…0016 0264 (×0.01) g/m3 6415…0016 6464 (×0.01) gr/ft3

x

0017…0018 0265 (×0.01) g/kg

6417…0018 6465 (×0.01) gr/lb

h

0019…0020 0266 (×0.01) kJ/kg 6419…0020 6466 (×0.01) btu/lb

Values read from the integer registers must be multiplied with the

provided multiplier to get the actual value. All integer values are signed.