Operation pressure object, Table 34 reliability, Table 35 event state – Vaisala GMW90 User Manual

Page 94: Table 37 status flags

Advertising
background image

User's Guide _______________________________________________________________________

92 ___________________________________________________________________ M211659EN-B

Table 34

Reliability

State

Cause

0 NO_FAULT_DETECTED

1 NO_SENSOR

No contact to measurement module

2 OVER_RANGE

RH over 100%

3 UNDER_RANGE

RH under 0%

7 UNRELIABLE_OTHER

Other measurement error

Table 35

Event State

State

Cause

0 NORMAL

Reliability equals 0 (NO FAULT DETECTED)

1 FAULT

Reliability not 0

Operation Pressure Object

Set current atmospheric pressure to improve the calculation accuracy of

pressure dependent humidity parameters.

NOTE

Pressure and Altitude objects are linked together. If Present Value in one

object is changed, Present Value in another object is changed

accordingly.

Table 36

Operation Pressure Object Properties

Property

Data type

Writable

Value or Initial Value

Object Identifier

BACnet Object Identifier

No

00 80 00 01 (hex)

Object Type = 2,

Instance = 1

Object Name

Character String

No

"OPER P"

Object Type

BACnet Object Type

No

2 (Analog Value)

Present Value

Real

Yes

1013.25

Description

Character String

No

"Operation Pressure"

Units

BACnet Engineering Units

No

133 (hectopascals)

Status Flags

BACnet Status Flags

No

0 (FAULT == FALSE)

Event State

BACnet Event State

No

0 (NORMAL,

does not change)

Out of Service

BOOLEAN

No

0 (FALSE)

Table 37

Status Flags

Flag

State

Cause

IN_ALARM

FALSE

Always FALSE

FAULT

FALSE

Always FALSE

OVERRIDDEN

FALSE

Always FALSE

OUT_OF_SERVICE

FALSE

Always FALSE