Calculated humidity objects, Table 31 calculated humidity objects, Table 32 calculated humidity object properties – Vaisala GMW90 User Manual

Page 93: Table 33 status flags

Advertising
background image

Appendix A _________________________________________________________ BACnet Reference

VAISALA ________________________________________________________________________ 91

Calculated Humidity Objects

Table 31

Calculated Humidity Objects

Instance

Name

Description

Unit

4

"Td"

"Dewpoint"

62/64 (ºC/ ºF)

5

"Tdf"

"Dewpoint"

62/64 (ºC/ ºF)

6

"dTd"

"Dewpoint depression"

121/120 (ΔºK/ ΔºF)

7

"Tw"

"Wet bulb temperature"

62/64 (ºC/ ºF)

8

"a"

"Absolute humidity"

217/2000 grams-per-cubic-meter / grains-per-cubic-foot

(Vaisala defined unit)

9

"x"

"Mixing ratio"

28/2001 grams-of-water-per-kilogram-dry-air / grains-of-

water-per-pound (Vaisala defined unit)

10

"h"

"Enthalpy"

149/24 kilojoules-per-kilogram-dry-air / btus-per-pound-of-

dry-air

Table 32

Calculated Humidity Object Properties

Property

Data type

(Application Type)

Writable

(Conformance

Code)

Value or Initial Value

Persistence

Object_Identifier

BACnetObjectIdentifier

No (R)

00 00 00 xx (hex)

Object Type = 0,

Instance = x

See Table 31 above.

Nonvolatile

Object_Name

CharacterString

No (R)

See Table 31 above.

Nonvolatile

Object_Type

BACnetObjectType

(ENUMERATED)

No (R)

0 (Analog Input)

Fixed

Present_Value

Real

Yes

(When Oos) (R)

0.0

Volatile

Description

CharacterString

No (O)

See table above

Nonvolatile

Units

BACnetEngineeringUnits

(ENUMERATED)

No (R)

See table above

Nonvolatile

Status_Flags

BACnet Status Flags (BIT

STRING)

Yes (when OoS)

(R)

0 (FAULT == FALSE)

Volatile

Reliability

BACnet Reliability

(ENUMERATED)

Yes (when OoS)

(O)

0 (NO FAULT DETECTED) Volatile

Event State

BACnetEventState

(ENUMERATED)

No (R)

0 (NORMAL)

Volatile

Out_of_Service

BOOLEAN

Yes (R)

0 (FALSE)

Volatile

COV_Increment

Real

Yes (O)

NaN (COV reporting

disabled)

Nonvolatile

Table 33

Status Flags

Flag

State

Cause

IN_ALARM

FALSE

Event State equals 0 (NORMAL)

TRUE

Event State not 0

FAULT

FALSE

Reliability equals 0 (NO FAULT DETECTED)

TRUE

Reliability not 0

OVERRIDDEN

FALSE

Always FALSE

OUT_OF_SERVICE FALSE

Present Value may NOT be written via BACnet

TRUE

Present Value may be written via BACnet