Chapter 7 _____________________________________________________________ Technical Data

VAISALA ________________________________________________________________________ 79

CHAPTER 7

TECHNICAL DATA

This chapter provides the technical data of the GMW90 series

transmitters.

Specifications

Table 13

Performance

Property

Description / Value

Carbon dioxide

Measurement range

0 … 5000 ppm

Accuracy

+20 … +30 °C (+ 68 … + 86 °F)

± (30 ppm + 2 % of reading)

+10 ... +20 °C, +30 ... +40 °C

(+50 ... +68 °F, +86 ... +104 °F)

± (35 ppm + 2.7 % of reading)

-5 ... +10 °C, +40 ... +55°C

(+23 ... +50 °F, +104 ... +131 °F)

± (45 ppm + 3.8 % of reading)

Stability in typical HVAC applications

Total accuracy at room temperature

±75 ppm at 600 and 1000 ppm

including 5 years drift*

Carbon dioxide sensor

Vaisala CARBOCAP

®

GM10

Temperature

Measurement range

-5 ... +55 °C (+23 ... +131 ºF)

Accuracy

+20 ... +30 °C (+68 ... +86 °F)

±0.5 °C (± 0.9 °F)

+10 ... +20 °C, +30 ... +40°C

(+50 ... +68 °F, +86 ... +104 °F)

±0.6 °C (± 1.08 °F)

-5 ... +10 °C, +40...+55°C

(+23 ... +50 °F, +104 ... +131 °F)

±0.8 °C (± 1.44 °F)

Temperature sensor

Digital temperature sensor

Relative humidity

Measurement range

0 ... 95 %RH, non-condensing

Accuracy

Temperature range +10 ... +40 °C

(+50 ... +104 °F)

0 ... 60 %RH

±2.5 %RH

60 ...80 %RH

±3.0 %RH

80 ... 95 %RH

±4.0 %RH

Temperature range -5 ... +10 °C,

+40 ... + 55 °C (+23 ... +50 °F,

+104 ... +131°F)

0 ... 60 %RH

±3.5 %RH

60 ...80 %RH

±4.0 %RH

80 ... 95 %RH

±5.0 %RH

Stability in typical HVAC applications

±0.5 %RH/year

Humidity sensor

Vaisala HUMICAP

®

180R

*Complies with CEC-400-2008-001-CMF