Set co2 indicator led parameters, Set co, Indicator led parameters – Vaisala GMW90 User Manual

Page 64

Advertising
background image

User's Guide _______________________________________________________________________

62 ___________________________________________________________________ M211659EN-B

Example (change Description to main_hall, and reinitialize the BACnet

stack):

>pass 9000

>bacnet description main_hall

Description : main_hall

>bacnet reinit

Reinitialize signaled to BACnet stack.

Set CO

2

Indicator LED Parameters

On transmitter models with indicator LEDs, you can use the TRAF

command to show or set CO

2

indicator LED limits. You can also turn the

LEDs off.

TRAF [step1 step2 step3]<cr>

TRAF [quant]<cr>

where
step1 = The yellow LED is lit above this ppm limit (default 800).

step2 = The red LED is lit above this ppm limit (default 1200).

step3 = The red LED starts blinking above this ppm limit

(default 5000).

quant = Quantity that controls the LEDs. Options are:

CO2 – LEDs controlled by CO2 level (default).

NONE – LEDs disabled.

Example (set indicator LED limits to 900, 1500 and 5000 ppm):

>traf 900 1500 5000

Traffic quantity : CO2

Traffic step 1 : 900.00 ppm

Traffic step 2 : 1500.00 ppm

Traffic step 3 : 5000.00 ppm

Traffic threshold : 20.00 ppm

>

Example (disable indicator LEDs):

>traf none

Traffic quantity : Disabled

Traffic step 1 : 800.00 ppm

Traffic step 2 : 1200.00 ppm

Traffic step 3 : 5000.00 ppm

Traffic threshold : 20.00 ppm

>