Set BACnet Parameters

Use the BACNET command to show or set some of the transmitter’s

BACnet parameters. You can also use the BACNET command to

reinitialize the BACnet stack of the transmitter without having to reset or

power cycle the transmitter.

BACNET [parameter_name [parameter_value]] [reinit]<cr>

where
parameter_name = Name of the BACnet parameter to change.

Available parameters are:
Instance: BACnet instance number. Unsigned value

in range 0 ... 4194302.
Name: BACnet Object_Name shown in the Device

object. String value, no spaces.
Description: BACnet Description shown in the

Device object. String value, no spaces.
Location: BACnet Location shown in the Device

object. String value, no spaces.
Password: Password used in ReinitializeDevice

service. String value, no spaces.
MAX_MASTER: Max_Master parameter in Device

object. Unsigned value, range 1 ... 127.

parameter_value = New value of the parameter. See descriptions above

for allowed values.

reinit

= Reinitializes the BACnet stack. Must be given as the

only argument for the BACNET command.

Example (show BACnet parameters):

>pass 9000

>bacnet

Instance : 6 (00000006h)

Name : GMW95R_ H2930002

Location : Location

Description : Description

Password : 1234

MAX_MASTER : 127 (007Fh)

COV_Interval : 0

Autobaud_Interval : 10