Temperature Object

Table 23

Temperature Object Properties

Property

Data type

(Application Type)

Writable

(Conformance

Code)

Value or Initial Value

Persistence

Object_Identifier

BACnetObjectIdentifier

No (R)

00 00 00 03 (hex)

Object Type = 0,

Instance = 3

Nonvolatile

Object_Name

CharacterString

No (R)

"T"

Nonvolatile

Object_Type

BACnetObjectType

(ENUMERATED)

No (R)

0 (Analog Input)

Fixed

Present_Value

Real

Yes

(When Oos) (R)

0.0

Volatile

Description

CharacterString

No (O)

"Temperature"

Nonvolatile

Units

BACnetEngineeringUnits

(ENUMERATED)

Yes (R)

62 (degrees-Celsius)

Possible units are

C (62) or F (64).

Nonvolatile

Status_Flags

BACnet Status Flags (BIT

STRING)

Yes (when OoS)

(R)

0 (FAULT == FALSE)

Volatile

Reliability

BACnet Reliability

(ENUMERATED)

Yes (when OoS)

(O)

0 (NO FAULT

DETECTED)

Volatile

Event State

BACnetEventState

(ENUMERATED)

No (R)

0 (NORMAL)

Volatile

Out_of_Service

BOOLEAN

Yes (R)

0 (FALSE)

Volatile

COV_Increment

Real

Yes (O)

NaN (COV reporting

disabled)

Nonvolatile

Min_Pres_Value

Real

No (O)

-40.0 (same as limit for

UNDER_RANGE)

Nonvolatile

Max_Pres_Value Real

No (O)

+80.0 (same as limit for

OVER_RANGE)

Nonvolatile

Table 24

Status Flags

Flag

State

Cause

IN_ALARM

FALSE

Event State equals 0 (NORMAL)

TRUE

Event State not 0

FAULT

FALSE

Reliability equals 0 (NO FAULT DETECTED)

TRUE

Reliability not 0

OVERRIDDEN

FALSE

Always FALSE

OUT_OF_SERVICE

FALSE

Present Value may NOT be written via BACnet

TRUE

Present Value may be written via BACnet

Table 25

Reliability

State

Cause

0 NO_FAULT_DETECTED

1 NO_SENSOR

No contact to measurement module

2 OVER_RANGE

T over +80 °C

3 UNDER_RANGE

T under -40 °C

7 UNRELIABLE_OTHER

Other measurement error

Table 26

Event State

State

Cause

0 NORMAL

Reliability equals 0 (NO FAULT DETECTED)

1 FAULT

Reliability not 0