Appendix A _________________________________________________________ BACnet Reference

VAISALA ________________________________________________________________________ 87

Property

Data type (Application

Type)

Writable

(Conforma

nce Code)

Value or Initial Value

Persistence

Max_APDU_Length_Ac

cepted

Unsigned16

N (R)

244

Fixed

Max_Master

Unsigned16 (1..127)

Y (R/O)

127

Nonvolatile

Max_Info_Frames

Unsigned

N (R/O)

1

Fixed

Segmentation_Supporte

d

BACnetSegmentation

(ENUMERATED)

N (R)

3 (No segmentation)

Fixed

APDU_Timeout

Unsigned

N (R)

3000 (ms)

Fixed

APDU_Retries

Unsigned

N (R)

0

Fixed

Device_Address_Bindin

g

List of

BACnetAddressBinding

N (R)

NULL

Fixed

Database_Revision

Unsigned

N (R)

0

Volatile

Object_Identifier: Must be unique in BACnet network. As Object

Identifier is 22 bits long its value range is 0 ... 4194303. Each device is

assigned a random value in this range at Vaisala factory.

Object_Name: Must be unique in BACnet network. Default object name

contains the name and serial number of the device. For example,

transmitter model GMW95 with serial number G1234567 receives the

default object name "GMW95_G1234567".

System_Status: System status can be OPERATIONAL (0) or

NON-OPERATIONAL (4). Device goes to NON-OPERATIONAL state

in case of fatal error.

Protocol_Services: Who-Is, I-Am, Who-Has, I-Have and

UnconfirmedCOVNotification services are available only when XMW90

is MS/TP master. Reinitialize Device service must be password

protected. According to BACnet protocol, password is character string

having max 20 characters. Default password is "1234". Password can be

changed through the service port by using the BACNET command. See

section Set BACnet Parameters on page 61.

Database_revision: This is changed during operation according to

section 12.11.35 of ANSI/ASHRAE standard 135-2008.