Firmware Version 5.2

The Controller Settings screen appears.

Make the following adjustments:

• Flow Meter Calibration
Calibration value representing the number of pulses that equal one-gallon of product flow through the
controlling system.

• Flow Control Delay
Setting that specifies a period of time from master switch on and the start of product application to the first
flow control correction. This setting can be used to eliminate unwanted correction of flow control at the start
of each pass. Typical setting values are 1 –2 seconds for liquid application control.

• Control Valve Settings
Opens the Control Valve Settings screen, which displays control valve settings for PWM, Servo, Calibrated
Reflow and Ramsey Valve Controls. For more information, see below or for more settings see

“Control

Valve Settings - Servo, Calibrated Reflow and Ramsey Valve” on page

223

.

• Close Flow Control Valve When Rate Off
When this is selected, the controlling system shuts down when there is either a zero rate in the field or when
entering an already-applied area. When unchecked, the controlling system remains in the last known state
when the sections are shut off.

• Auxiliary Valve 1 & 2
When all boom sections are off, this setting closes or opens an auxiliary valve. Choose settings for up to
two auxiliary valves.

• Allowable Error
Determines the percent of error that is allowed prior to the product control system making any flow rate
changes.

• Threshhold
The user-defined percentage of actual rate error allowed before an alarm sounds.

• Timeout
The number of seconds that an actual rate falls out of the error threshold before an alarm sounds.

120 pls/gal

Control Valve

Settings

Flow Meter Calibration

Flow Control Delay

0 s

Rate Off

Flow Control Valve

Hole

Auxiliary Valve 1

Close

Auxiliary Valve 2

Close

Rate Error Alarm

Threshold

30 %

Timeout

5 s

Controller Settings