Discharge flow sensor pin outs, Direct injection: inlet restriction, Vacuum switch pin outs – Kinze Ag Leader Integra User Manual

Page 273: Pump calibration setting, Ischarge, Ensor, Acuum, Witch

Advertising
background image

257

A

PPLICATION

I

NJECTION

D

ISCHARGE

F

LOW

S

ENSOR

P

IN

O

UTS

Direct Injection: Inlet Restriction

The injection pump has a vacuum switch that is used to warn operators of any
restriction at the inlet of the pump. The sensor is a normally closed switch that
opens if a restriction is encountered in the injection system. A warning will be
displayed for the operator if the vacuum switch opens due to restriction. See
table below for pin locations. The operator can test the system by unplugging
the sensor, which will trigger the warning. If the operator jumps pins A and C,
the warning will end.

V

ACUUM

S

WITCH

P

IN

O

UTS

Controller Settings: Direct Injection Pump Calibration

Pump Calibration Setting

• Factory Calibration
The Factory Calibration Number is found on the tag of the Digital Pump Speed Sensor. This tag number
represents pulses per 10 fluid ounces. Divide the tag number by 10 and enter this number. Once entered,
this number should not be changed.

• Perform Calibration
Press the Perform Calibration button to begin the calibration procedure for the Direct Injection pump. The
pump will not run until this calibration has been performed.

Module Auxiliary Connection 12-

Pin Socket

3-Pin WP Shroud

Power (12V)

11

A

Signal

9

B

Ground

8

C

Module Auxiliary Connection 12-

Pin Socket

3-Pin WP Shroud

Power (12V)

2

C

Signal

10

A

Make sure 3 way

valve is in operate

Check for plugged

strainer on the inlet of

Refer to injection pump

manual to test vacuum