304

Firmware Version 5.2

press the In-Field Calibration button on the Strip-Till Control screen, and the In-Field CFR Calibration
Wizard appears.

1. Select Metering Circuit to Calibrate

Use the drop-down menu to select the channel to calibrate, and press

to continue.

2. Enter Actual Weight

The Accumulated Weight is shown in the top portion of the screen. Press

to enter the Actual

Weight, and press

to continue.

3. Calibration Complete

A message appears, stating that your calibration is complete, and showing the CFR amount, in cubic feet

per revolution. Press

to finish the calibration.

Strip Till Control: Auxiliary Tab

• Fan Speed Cal
Number of pulses that are generated by the sensor
during one revolution of the blower fan shaft.

• Min Speed
Setting represents the desired minimum speed of the
blower fan. An alarm will sound if the blower fan speed
falls below this value.

• Max Speed
Setting represents the desired maximum speed of the
blower fan. An alarm will sound if the blower fan speed
exceeds this value.

• Rate Threshold

Percentage difference between the Actual Rate and the Target Rate when the Rate Not Responding
Message is displayed on the Run screen.

• Low Fan Speed Shutoff
When selected, granular product application of a strip-till toolbar will be shut off if fan speed drops below
the Min Speed setting.

T

ROUBLESHOOTING

D

IRECT

C

OMMAND

G

RANULAR

A

PPLICATIONS

Problem: Run screen Granular channel(s) green light spreader indicator will not turn on

Solution:

1. Make sure ground speed is registered a value greater than zero on the display.

2. Verify a target rate greater than zero is entered into the display.

3. Check the switch status found on the Run screen under System and Input Diagnostics. As the

master switch is turned on and off, the Input Diagnostics window should change from black to
green (if they do not, then refer to the installation instructions to verify switch connections).

4. Check high current connection into the Granular Control Module.

Problem: Master switch will not turn on when the foot pedal is on.

Solution: Make sure the Master Switch Input is set to “External 2” under the Auxiliary Input

Settings.

Channel 1

Channel 2

Channel 3

Auxiliary

Fan

Fan Speed Cal

Min Speed

Max Speed

Rate Not Responding Threshold

Rate Threshold

30 %

Low Fan Speed
Shutoff

Strip Till Control

4 pls/rev

0 rpm

6000 rpm