Technical data

3-2

L

BA2141 EN 1.0

3.3

Rated data

Field

Values

Voltage supply

24 V DC

ñ 10 %; max. 120 mA

Communication profile

LONMARK

®

Functional Profile “Variable Speed Motor Drive”

Communication medium

FTT - 10 A (Free Topology Transceiver)

Insulation voltage between bus and ...

Rated insulation voltage

Insulation type

Earth reference / PE

50 V AC

Mains isolation

External supply (terminal 39/59)

50 V AC

Mains isolation

Power stage

– 820X / 821X

270 V AC

Basic insulation

– 822X / 8200 vector

270 V AC

Double insulation

– 93XX

270 V AC

Double insulation

Control terminals

– 820X / 8200 vector (with internal supply)

0 V AC

No mains isolation

– 8200 vector (with external supply

100 V AC

Basic insulation

– 821X

50 V AC

Mains isolation

– 822X

270 V AC

Basic insulation

– 93XX

270 V AC

Basic insulation

Degree of pollution

VDE0110, part 2, pollution degree 2

3.4

Dimensions

Service

LON

L

24V DC

FTT

2141

62

75

18
23

Fig. 3-1

Dimensions of the 2141 fieldbus module (all dimensions in mm)

Show/Hide Bookmarks