3 node object, 1 inhibit / enable all objects, 2 status messages – Lenze EMF2141IB User Manual

Page 26: Inhibit / enable all objects, Status messages, Parameter setting

Advertising
background image

Parameter setting

6-4

L

BA2141 EN 1.0

Details about the
parameter data

5th byte

parameter data

telegram:

Service

Order type

1 = Read

2 = Write

Data contents

Response ok
– Read: 1
– Write: 2

Faulty response
– Read: 81

hex

(80

hex

+ 1)

– Write: 82

hex

(80

hex

+ 2)

Details about the
parameter data

6th byte

7th byte

8th byte

9th byte

parameter data

telegram:

Data 4

Data 3

Data 2

Data 1

Bytes 6 to 9 contain the data to be written.

Bytes 6 to 9 are not relevant for reading orders.

The parameters of the corresponding code are changed by multiplying the parameter value with
10000 (the result is an integer value). Lenze parameters are mainly in the fixed-point format ,data
type Integer32, with four decimal codes.

Tip!

Please see the Operating Instructions for your controller for the value range of Lenze codes.

Lenze parameters

dec

hex

Example: Set C0039 (JOG) = 150.4 Hz

150.4 x 10000 = 1504000

= 0016F300

The parameter value needs 1 to 4 bytes depending on the data format (see “ Attribute table” in the
Operating Instructions for your controller)

6th byte

7th byte

8th byte

9th byte

Data 4

Data 3

Data 2

Data 1

High byte

Low byte

High byte

Low byte

High word

Low word

Double word

Assignment of bytes 6 to 9 with parameter value of different lengths

6th byte

7th byte

8th byte

9th byte

00

00

00

Parameter value (length 1)

00

00

Parameter value (length 2)

Parameter value (length 4)