4 network variable for 93xx controllers, Network variable for 93xx controllers, Parameter setting – Lenze EMF2141IB User Manual

Page 57: 2 control word for 82xx, Show/hide bookmarks

Advertising
background image

Parameter setting

6-35

L

BA2141 EN 1.0

6.5.2.2

Control word for 82XX

Bit

820X

821x,822x

Bit

820X

821x,822x

00,

00 = C0046 active
01 = JOG1 active in C0037

00 = C0046 active
01 = JOG1 active in C0037

00,
01

10 = JOG2 active in C0038
11 = JOG3 active in C0039

01 JOG1 active in C0037
10 = JOG2 active in C0038
11 = JOG3 active in C0039

02

CW/CCW (CW rotation/CCW rotation)
0 = CW rotation
1 = CCW rotation

CW/CCW (CW rotation/CCW rotation)
0 = CW rotation
1 = CCW rotation

03

QSP (quick stop)
0 = QSP not active
1 = QSP active

QSP (quick stop)
0 = QSP not active
1 = QSP active

04

Reserved

RFG stop (stop of the ramp function generator)

0 = RFG stop not active

1 = RFG stop active

05

Reserved

RFG zero (deceleration along the T

if

ramp C0013)

0 = RFG zero not active

1 = RFG zero active

06

Reserved

UP function for motor potentiometer

0 = UP not active

1 = UP active

07

Reserved

DOWN function for motor potentiometer

0 = DOWN not active

1 = DOWN active

08

Reserved

Reserved

09

Ctrl. inhibit (controller inhibit)

0 = controller not inhibited

1 = controller inhibited

Ctrl. inhibit (controller inhibit)

0 = controller not inhibited

1 = controller inhibited

10

Reserved

Reserved

11

Reserved

TRIP reset

0 -> 1 = Edge from 0 to 1

12

PAR1 (Parameter set changeover)

0 -> 1 = Parameter set

1 -> 0 = Parameter set

PAR1 (Parameter set changeover)

0 -> 1 = Parameter set

1 -> 0 = Parameter set

13

Reserved

Reserved

14

DC brake (DC injection brake)

0 = DC brake not active

1 = DC brake active

DC brake (DC injection brake)

0 = DC brake not active

1 = DC brake active

15

Reserved

Reserved

2141LON010

AIF

C0046

.B15

.B13
.B14

.B12

.B0

.B1
.B2

.B3

.B4...

...

...

.B8

.B9

.B10

.B11

QSP

CINH

TRIP-SET

TRIP-RESET

16 Bit

16 Bit

0

JOG/

C046

0 1 1

0 1 0 1

PAR

GSB

R/L

Fig. 6-6

Access to control word and actual frequency in 82XX (fixed assignment)

Show/Hide Bookmarks

Advertising