Parameter setting

6-10

L

BA2141 EN 1.0

6.3

Node Object

6.3.1

Inhibit / Enable all objects

All objects can be inhibited or enabled via the network variable

nvi00Request

:

Inhibit:

nvi00Request.object_id

= Object no.

nvi00Request.object_request

= 1 (RQ_DISABLED)

Enable:

nvi00Request.object_id

= Object no.

nvi00Request.object_request

= 7 (RQ_ENABLED)

6.3.2

Status messages

In the event of a communication error between the LON interface module and the basic unit the bit
comm_failure will be set under

nvo00State.

Structure Type Definition:

typedef struct {

unsigned long object_id;
unsigned invalid_id : 1;
unsigned invalid_request : 1;
unsigned disabled : 1;
unsigned out_of_limits : 1;
unsigned open_circuits : 1;
unsigned out_of_service : 1;
unsigned mechanical fault : 1;
unsigned feedback_failure : 1;
unsigned over_range : 1;
unsigned under_range : 1;
unsigned electrical_fault : 1;
unsigned unable_to_measure : 1;
unsigned comm_failure : 1;
unsigned fail_self_test : 1;
unsigned self_test_in_progress : 1;
unsigned locked_out : 1;
unsigned manual_control: 1;
unsigned in_alarm: 1;
unsigned in_override: 1;
unsigned report_mask: 1;
unsigned programming_mode: 1;
unsigned programming_fail: 1;
unsigned alarm_notify_disabled: 1;
unsigned reserved1: 1;
unsigned reserved1: 8;

} SNVT_obj_status;