Parameter setting – Lenze EMF2141IB User Manual

Page 58

Advertising
background image

Parameter setting

6-36

L

BA2141 EN 1.0

6.5.3

Network variable for 8200 vector controllers

Setpoint source selection

The setpoint source for these controllers is selected under code C0001. An evaluation of process
data is only possible if code C0001 is set to ”3” when the controller is operated together with the
fieldbus module. (Selection: process data channel of a fieldbus module AIF-IN.W1 or AIF-IN.W2).

The process data channel which describes the frequency setpoint (C0046) and the control word
(parameter channel, C0135) is the setpoint source (see 8200 vector Operating Instructions).

Check under C0412/x whether the setpoint source is assigned to the signal wanted.

Tip!

Please ensure that code C0001 or C0410 is the same for all parameter sets.

Digital and analog input and output signals can be freely configured (see Operating Instructions for
8200 vector; codes C0410, C0412, C0417 and C0421) The change of the code C0001 to 3 starts the
preconfiguration of the process data words in the controller.