Parameter setting

6-12

L

BA2141 EN 1.0

6.4.1.2

Actual speed value

network output SNVT_lev_percent nvoDrvSpeed;

The output network variable indicates the current speed as proportion of the rated value. Display
value in [% ].

Output range

The possible bandwidth for the output variables is between –163.840% and 163.830% . Resolution:
0.005% .

The value +163.835% (7FFF

hex

) is assumed to be wrong.

Update rate

The variable is sent if the value changes or if the time set under

Maximum Send Time

(

nciSndHrtBt

)

has expired.

The variable value will not be sent quicker than set in

Minimum Send Time

(

nciNinOutTm

).

Standard Service Type

The Standard Service Type is acknowledged.

Function

The value of

nvoDrvSpeed

results from the AIF output data word 1 of the process data channel.

Since 82XX and 93XX send different value, the actual speed values are converted in different ways.

82XX controllers send actual values in [Hz] and a factor of 50 (24000 = 480Hz).

The value for

nvoDrvSpeed

results from:

nvoDrvSpeed =

AIFOut.W1

nciNmlFreq

10 [

NVfactor]

×

50[

AIFfactor]

Ч

100[% ]

Ч

200 [

NVfactor]

93XX controllers send actual values in [% ] and a factor of 163.83 (16383 = 100% ).

The value for

nvoDrvSpeed

results from:

nvoDrvSpeed =

AIFOut.W1

16383 [

NVfactor]

Ч

100[% ]

Ч

200 [

NVfactor]