8 rated frequency, Rated frequency, Parameter setting – Lenze EMF2141IB User Manual
Page 40: 2 receive heartbeat time
Advertising
Parameter setting
6-18
L
BA2141 EN 1.0
6.4.2.2
Receive Heartbeat Time
network input config SNVT_time_sec nciRcvHrtBt;
This configuration variable is used to store the time expected for an update, if this time expires
without an update, the values for the following network variables will be reset to their default settings:
nviDrvSpeedStpt
(
^
6-11)
nviDrvSpeedScale
(
^
6-13)
It is also used to monitor the variables configured in
nciAIFRecHrtBt
(
^
6-27)
. The variables are:
nviAIFStw
,
nviAIFIn1
,
nviAIFIn2
,
nviAIFIn3
.
Input range
The possible bandwidth for the configuration variable is between 0.0 and 6553.4 seconds (resolution
0.1 seconds)
Standard value
0.0 (no monitoring)
SCPT Reference
SCPTmaxRcvTime (48)