Parameter setting

6-25

L

BA2141 EN 1.0

6.4.2.9

Acceleration time

network input config SNVT_time_sec nciRampUpTm;

This configuration variable indicates the acceleration time of the motor.

Input range

The possible bandwidth for the configuration variable is between 0 and 6553.4 seconds (resolution
0,1 Sekunden)

Standard value

5 seconds

Function

After a change of the acceleration time, the value will be sent to the drive via the parameter channel
(code 0012, subcode 00).

SCPT Reference

SCPTrampUpTm (160)