Parameter setting

6-15

L

BA2141 EN 1.0

6.4.1.5

Motor voltage

network output SNVT_volt nvoDrvVolt;

The output network variable indicates the current output voltage in [Volt].

Output range

The possible bandwidth for the output variable is between –3276.8 V and +3276.6 V.
Resolution 0.1 V.

The value +3276.7 V (7FFF

hex

) is assumed to be wrong.

The typical output range is between 0 V and 700 V.

Update rate

The variable is sent if the value has changed.

The variable is sent as heart beat if the time set under

Configuration Property Maximum Send Time

(

nciSndHrtBt

) has expired.

The variable value will not be sent quicker than set in

Configuration Property Minimum Send Time

(

nciMinOutTm

).

Function

The current output voltage is cyclically read by the drive (code 0052, subcode 00). The value is
calculated as follows:

nvoDriveVolt =

SDF.LW

10000 [

AIFfactor]

×

10 [

NVfactor]

If an error occurs during the query,

nvoDrvVolt

is set to 7FFF

hex

.

Standard Service Type

The Standard Service Type is acknowledged.