Parameter setting

6-37

L

BA2141 EN 1.0

Network variable from drive (see function block AIF-OUT

(

^

6-38)

)

nvoAIFStatus

reads bits B0 ... B15 of the status word AIF-STAT

(

^

6-38)

Status word AIF-STAT

LOW byte

HIGH byte

Bits 0 to 7 of the status word will be entered here.

Bits 8 to 15 of the status words will be entered here.

nvoAifOut1

reads the output word AIF-OUT.W1

Actual value

LOW byte

HIGH byte

The actual frequency value with the signed normalisation 24000 = 480 Hz is provided here.

Torque values are normalised with 16384 = 100%. AIF-OUT.W1 see C0421/1, (Operating Instructions for 8200 vector)

nvoAifOut2

reads the output word AIF-OUT.W2

Actual value

LOW byte

HIGH byte

The actual frequency value with the signed normalisation 24000 = 480 Hz is provided here.

Torque values are normalised with 16384 = 100%. AIF-OUT.W2 see C0421/2, (Operating Instructions for 8200 vector)

Network variable to drive (see function block AIF-IN

(

^

6-40))

nviAIFStw

writes bits B0 ... B15 in the control word AIF-CTRL

(

^

6-39)

Control word AIF-CTRL

LOW byte

HIGH byte

Bits 0 to 7 of the control word will be entered here.

Bits 8 to 15 of the control word will be entered here.

nviAIFIn1

writes the input word AIF-IN.W1

AIF-IN.W1

LOW byte

HIGH byte

The frequency setpoint is preselected as process data word. The normalisation differs from the setting under C0046. It is a signed value, 24000

= 480 Hz. AIF-IN.W1 see C0412/x, Wert “10” (Operating Instructions for 8200 vector)

nviAIFIn2

writes the input word AIF-IN.W2

AIF-IN.W2

LOW byte

HIGH byte

The frequency setpoint is preselected as process data word.
The normalisation differs from the setting under C0046. It is a signed value, 24000 = 480 Hz.
AIF-IN.W2 see C0412/x, Wert “11” (Operating Instructions for 8200 vector)