Parameter setting

6-31

L

BA2141 EN 1.0

6.5.1.2

Input variable

network input SNVT_count nviAIFStw;

network input SNVT_count nviAIFIn1;

network input SNVT_count nviAIFIn2;

network input SNVT_count nviAIFIn3;

The input network variable

nviAIFStw

is directly accepted by the AIF control word.

The input network variables

nviAIFIn1

to

nviAIFIn3

are directly accepted by the corresponding

AIF input data words.

1Input range

The possible bandwidth for the output variable is between 0 and 65535.

Standard value

The standard value after a reset is 0 for all four variables.

The standard value for

nviAIFStw

is determined by the configuration properties

nciAIFDefStw

and

nciAIFRecHrtBt

.

nciAIFDefStw

indicates the function to be executed in the event of a

Receive Heartbeat Timeout

and

nciAIFRecHrtBt

indicates the variables monitored by a

Receive

Heartbeat

.

nciAIFRecHrtBt.bit0

= 1 – Timeout monitoring for

nviAIFStw

nciAIFRecHrtBt.bit1

= 1 – Timeout monitoring for

nviAIFIn1

nciAIFRecHrtBt.bit2

= 1 – Timeout monitoring for

nviAIFIn2

nciAIFRecHrtBt.bit3

= 1 – Timeout monitoring for

nviAIFIn3

nciAIFStw

= 0 – No reaction

nciAIFStw

= 1 – Quick stop

nciAIFStw

= 2 – Controller inhibit

If one of the monitored variables gets a

Receive Heartbeat Timeout

, the function selected in

nciAIFDefStw

will be carried out.

The quick stop functions sets bit 3 in the AIF control word, the controller inhibit function sets bit 9 in
the AIF control word. The functions quick stop and controller inhibit will only be reset after all
monitored variables have been updated within the Receive Timeouts.