Parameter setting

6-16

L

BA2141 EN 1.0

6.4.1.6

Operating time

network output SNVT_time_hour nvoDrvRunHours;

This network variable output the entire operating time in hours.

Output range

The possible bandwidth for the output variable is between 0 and 65534 hours. Resolution: 1 hour.

The value of 65535 hours (FFFF

hex

) is assumed to be wrong.

Update rate

The variable is sent if the value has changed.

The variable value will not be sent quicker than set im

Configuration Property Minimum Send Time

(

nciMinOutTm

).

Standard Service Type

The Standard Service Type is acknowledged.

Function

The operating time is cyclically read by the drive (code 0174, subcode 00).

82XX controllers send the operating time in hours with the AIF factor 10000 (30000 = 3 hours).

The value is calculated as follows:

nvoDriveRunHours =

SDF.LW

10000 [

AIFfactor]

×

1 [

NVfactor]

93XX controllers send the operating time in seconds without AIF factor.

The value is calculated as follows:

nvoDriveRunHours =

SDF.LW

3600 [

seconds

hour

]

×

1 [

NVfactor]

If an error occurs during the query,

nvoDrvRunHours

is set to FFFF

hex

.