Parameter setting

6-28

L

BA2141 EN 1.0

6.4.2.12

Monitoring reaction for AIF-CTRL

network input config SNVT_state nciAIFDefStw;

If one of the monitored variables of the AIF-CTRL gets a Receive Heartbeat Timeout

(

^

6-30)

, the

function selected in

nciAIFDefStw

will be carried out.

The quick stop functions sets bit 3 in the AIF control word, the controller inhibit function sets bit 9 in
the AIF control word.

Tip!

The functions quick stop and controller inhibit will only be reset after all monitored variables have
been updated within the Receive Heartbeat Timeout.

Input range

The possible bandwidth for the configuration variables is 0, 1 oooder 2

nciAIFDefStw

= 0 – No reaction

nciAIFDefStw

= 1 – Quick stop

nciAIFDefStw

= 2 – Controller inhibit

Standard value

0