Maximum speed
network input config SNVT_lev_percent nciMaxSpeed;
The configuration variable contains the maximum motor speed. The value is indicated as percentage
of the rated value (
NciNmlSpeed
).
Input range
The possible bandwidth for the configuration variable is between –163.840% and 163.830%
(resolution 0.005% ). The value +163.835% (7FFF
hex
) is assumed to be wrong.
The entered value will be checked by means of the following formula:
–163.840%
≤
Minimum speed
£
Maximum speed
≤
163.830%
If the result is wrong, the lower value is taken as maximum speed.
Standard value
100.000 %
Function
After a change of the maximum speed, the value will be sent to the drive via the parameter channel
(code 0011, subcode 00).
SCPT Reference
SCPTmaxSetpoint (50)