Installation, 3 connection diagram, 9english – Lenze ETMD Tmd frequency inverter User Manual

Page 10: Danger

Advertising
background image

9

ENGLISH

Installation

Observe the following when using E.l.c.b:

• Installation of E.l.c.b only between supplying mains and controller.
• The E.l.c.b can be activated by:

- capacitive leakage currents between the cable screens during operation (especially with long,

screened motor cables)

- connecting several controllers to the mains at the same time

- RFI filters

3.2.3 Connection diagram

AIN

AIN

COM

U V W

L1 L2

9 A+ A1

20

20

E1 E2 E3

71

62

7

72

COM

COM

+12 V

+15 V

+15 V

+10 V

8U

8U

7

+

_

28 7

L3

7

28 E1 E2 E3 E4

E4 A2

AOUT

TXA

TXB

COM

DIGOUT

DIGOUT

PE

N

L3

L2

L1

3/PE 320V 0 % 528V + 0 %

48 Hz 62 Hz

PES

PE

PES

PES

M

3~

PES

PE

0 … +5 V

0 … +10 V

-10 … +10 V

0 … 20 mA

4 … 20 mA

1k …10k

+12 V DC - 0 %

+30 V DC + 0 %

L1

L2

PE

N

L3

L2

L1

3/PE 180V 0% 264V + 0 %

48 Hz 62 Hz

L3

L2/N

PE

N

L3

L2

L1

2/PE 180V 0% 264V + 0 %

48 Hz 62 Hz

L1

PE

N

L3

L2

L1

1/N/PE 180V 0% 264V + 0 %

48 Hz 62 Hz

L2/N

L1

8I

0 5 Nm/4 5 lb in

6 mm/0 24 in

1 2 Nm/10 lb n

9 mm/0 35 in

0 2 Nm/2 b in

6 mm/0 24 in

< 1mm²/AWG 26 16

Tmd003

DANGER!

• Hazard of electrical shock! Circuit potentials are up to 480 VAC above earth ground.

Capacitors retain charge after power is removed. Disconnect power and wait until
the voltage between B+ and B- is 0 VDC before servicing the drive.

• Do not connect mains power to the output terminals (U,V,W)! Severe damage to the

drive will result.

• Do not cycle mains power more than once every three minutes. Damage to the
drive will result.