Troubleshooting and fault elimination

(1) The drive can only be restarted if the error message has been reset; see c70

Error

Cause

Remedy

(1)

External error

Digital input “TRIP set” is active

Remove external error

0

Internal fault

Please contact Lenze

Communication error

Serial timer has timed out

Check serial link connections

Communication error

Serial communication failure

Please contact Lenze

Remote keypad fault

Remote keypad disconnected

Check remote keypad connections

1

Drive identification fault

Attempt was made to perform motor
calibration before setting C86...C91

Must set C86...C91 before performing
motor calibration (see c48)

1

Short-circuit or overload

Short-circuit

Find reason for short-circuit; check
motor cable

Excessive capacitive charging
current of the motor cable

Use shorter motor cables with lower
charging current

Acceleration time (C12, c01) too short

• Increase acceleration time
• Check controller selection

Defective motor cable

Check wiring

Internal fault in motor

Check motor

Frequent and long overload

Check controller selection

Earth fault

Grounded motor phase

Check motor/motor cable

Excessive capacitive charging
current of the motor cable

Use shorter motor cables with lower
charging current

C

Motor overload (I

2

t

overload)

Motor is thermally overloaded, due to:
• impermissable continuous current
• frequent or too long acceleration

processes

• Check controller selection
• Check setting of c20

LP1

Loss of motor phase

Open-circuit on controller output when in
vector mode (C14 = 4, 5)

• Motor must be connected in vector

mode

• Check motor/motor cable

H

Controller
overtemperature

Controller too hot inside

• Reduce controller load
• Improve cooling

U

Overvoltage on DC bus

Mains voltage too high

Check mains voltage

Excessively short deceleration time or
motor in generator mode

Increase deceleration time or use
dynamic braking option

Earth leakage on the motor side

Check motor/motor cable
(separate motor from controller)

Flying restart fault

Controller was unable to synchronize with
motor during restart attempt

Check motor/load

Faulty auto-TRIP reset

More than 8 errors in 10 minutes

Depends on the error

Loss of 4-20 mA
reference

4-20 mA signal (terminal 8I) is below 2
mA (C34 = 5)

Check signal/signal wire

Single phase fault

A mains phase has been lost

Check mains voltage