Commissioning, 17 english – Lenze ETMD Tmd frequency inverter User Manual

Page 18

Advertising
background image

17

ENGLISH

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze Selection

Acceleration time 2

5.0

0.0

{s}

999 • Activated using CE1...CE4

• c01 = frequency change 0 Hz...C11
• c03 = frequency change C11...0 Hz
• For S-ramp accel/decel, adjust c82

Deceleration time 2

5.0

0.0

{s}

999

Holding time -
automatic DC injection
brake (Auto-DCB)

0.0

0.0

{s}

999

0.0 = not active

999 = continuous brake

• Automatic motor braking after

by

means of motor DC current for the entire
holding time (afterwards: U, V, W inhibited)

• Confirm motor suitability for use with DC

braking

Analog output scaling

100

0.0

999 When 10 VDC is output at terminal 62, it will

equal this value (see c11)

Configuration -
Analog output (62)

0

0

None

1

Output frequency 0-10 VDC

Use c08 to scale signal

Example:

c11 = 1 and c08 = 100:

At 50 Hz, terminal 62 = 5 VDC
At 100 Hz, terminal 62 = 10 VDC

2

Output frequency 2-10 VDC

3

Load 0-10 VDC

4

Load 2-10 VDC

5

Dynamic braking

Only used with DB option

Configuration - Digital
output (A1)

0

Output is energized if

0

Ready

1

Fault

2

Motor is running

3

Motor is running - CW rotation

4

Motor is running - CCW rotation

5

Output frequency = 0 Hz

6

Frequency setpoint reached

7

Frequency threshold (C17) exceeded

8

Current limit (motor or generator
mode) reached

Configuration - Digital
output (A2)

1

I2t switch-off (thermal
motor monitoring)

100

30

{%}

100

100% =

Tmd

rated output current

• Triggers

fault when motor current

exceeds c20 for too long

• Correct setting = (motor nameplate current)

/ (Tmd output current rating) X 100%

Example

: motor = 6.4 amps and

Tmd = 7.0 amps; correct setting = 91%
(6.4 / 7.0 = 0.91 x 100% = 91%)

WARNING!

Maximum setting is rated motor current (see nameplate). Does not provide full motor
protection!

Advertising