Commissioning

4.2

Electronic programming module (EPM)

The EPM contains the controller’s memory. Whenever parameter settings are changed,
the values are stored in the EPM. It can be removed, but must be installed for the
controller to operate (a missing EPM will trigger an fault). The controller ships with
protective tape over the EPM that can be removed after installation.

An optional EPM Programmer (model ESMD01EP; manual EP03) is available that allows: the controller to
be programmed without power; OEM settings to be default settings; fast copying of EPMs when multiple
controllers require identical settings. It can also store up to 60 custom parameter files for even faster
controller programming.

Tmd004

Tmd007

4

Commissioning

4.1

Parameter setting

Status/fault messages

Change parameters

Note

If the password function is enabled, the password must be entered into C00 to access
the parameters. C00 will not appear unless the password function is enabled. See C94.