Technical data, 2technical data, 1 standards and application conditions – Lenze ETMD Tmd frequency inverter User Manual

Page 6: 5english

Advertising
background image

5

ENGLISH

Technical Data

Conformity

CE

Low Voltage Directive (2006/95/EC)

Approvals

UL 508C

Underwriters Laboratories - Power Conversion Equipment

Max. permissible motor cable
length

(1)

shielded:

50 m (low-capacitance)

unshielded:

100 m

Input voltage phase imbalance

< 2%

Humidity

< 95% non-condensing

Output frequency

0...240 Hz

Environmental conditions

Class 3K3 to EN 50178

Temperature range

Transport

-25 … +70 °C

Storage

-20 … +70 °C

Operation

0 … +55 °C (with 2.5 %/°C current derating above +40 °C)

Installation height

0 … 4000 m a.m.s.l. (with 5 %/1000 m current derating above 1000 m a.m.s.l.)

Vibration resistance

acceleration resistant up to 0.7 g

Earth leakage current

> 3.5 mA to PE

Enclosure (EN 60529)

IP 20

Protection measures against

short circuit, earth fault, overvoltage, motor stalling, motor overload

Operation in public supply networks
(Limitation of harmonic currents
according to EN 61000-3-2)

Total power

connected to

the mains

Compliance with the requirements

(2)

< 0.5 kW

With mains choke

0.5 … 1 kW

With active filter (in preparation)

> 1 kW

Without additional measures

(1) For compliance with EMC regulations, the permissible cable lengths may change.
(2) The additional measures described only ensure that the controllers meet the requirements of the EN 61000-3-2.

The machine/system manufacturer is responsible for the compliance with the regulations of the machine!

2

Technical data

2.1

Standards and application conditions

Advertising