Installation, 8english, Bc d a e – Lenze ETMD Tmd frequency inverter User Manual

Page 9

Advertising
background image

8

ENGLISH

Installation

Type

Installation to EN 60204-1

Installation to UL

E.l.c.b.

(2)

Fuse

Miniature

circuit

breaker

L1, L2, L3, PE

[mm²]

Fuse

(3)

L1, L2, L3, PE

[AWG]

1/N/PE

ETMD371L2YXA, ETMD551L2YXA

M10 A

C10 A

1.5

10 A

14

> 30 mA

ETMD751L2YXA

M16 A

C16 A

2.5

15 A

14

ETMD112L2YXA

M20 A

C20 A

2.5

15 A

12

ETMD152L2YXA

M25 A

C25 A

2.5

20 A

12

ETMD222L2YXA

M30 A

C30 A

4.0

30 A

10

3/PE

ETMD371L2YXA...ETMD112L2_XA

(4)

M10 A

C10 A

1.5

10 A

14

ETMD152L2_XA

(4)

M16 A

C16 A

1.5

12 A

14

ETMD222L2_XA

(4)

M16 A

C16 A

2.5

15 A

12

ETMD402L2TXA

M25 A

C25 A

4.0

25 A

10

ETMD552L2TXA

M40 A

C40 A

6.0

35 A

8

ETMD752L2TXA

M50 A

C50 A

10

45 A

8

ETMD371L4TXA...ETMD222L4TXA

M10 A

C10 A

1.5

10 A

14

ETMD302L4TXA

M16 A

C16 A

1.5

12 A

14

ETMD402L4TXA

M16 A

C16 A

2.5

15 A

14

ETMD552L4TXA

M20 A

C20 A

2.5

20 A

12

ETMD752L4TXA

M25 A

C25 A

4.0

25 A

10

(1) Observe the applicable local regulations
(2) Pulse-current or universal-current sensitive earth leakage circuit breaker
(3) UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, required. Bussman KTK-R, JJN, JJS, or equivalent
(4) “_” = Y or T; the ratings are the same for either model with 3/PE input

EMC

Compliance with EN 61800-3/A11

Noise emission
Compliance with limit value class A according to EN 55011 if installed in a control
cabinet with the appropriate footprint filter and the motor cable length does not exceed
10m

A Screen clamps

B Control cable

C Low-capacitance motor cable

(core/core < 75 pF/m, core/screen < 150 pF/m)

D Electrically conductive mounting plate

E Filter

Tmd005

B

C

D

A

E

3.2.2 Fuses/cable cross-sections

3.2

Electrical installation

3.2.1 Installation according to EMC requirements

(1)