Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze Selection

Vector speed control
loop gain

30.0

0.0

100 Optimizes dynamic performance in vector

mode

Vector speed stability

30.0

0.0

100 Optimizes steady-state speed stability in

vector mode

7

I

max

gain

0.25

0.00

16.0 For most applications, there is no need to

change the Lenze settings

(1)

Integral action time

65

12

{ms}

9990

Motor stator resistance 0.00

0.00

{

}

64.0 Will be automatically programmed by c48

(1)

Motor rated power

0.00

{kW}

99.9 • Set to motor nameplate kW

• Lenze setting = Tmd rated kW

7

Motor rated speed

1390 300

{RPM}

65000 Set to motor nameplate speed

Motor rated current

0.0

0.0

{A}

480 Set to motor nameplate current

Motor rated frequency

50

10

{Hz}

999 Set to motor nameplate frequency

Motor rated voltage

0

0

{V}

600 Set to motor nameplate voltage

1

Motor cosine phi

0.80

0.40

1.00 Set to motor power factor

Note

If motor power factor is not known, use the following formulas:
cos phi = motor Watts / (motor efficiency X C90 X C88 X 1.732)
cos phi = cos [ sin-1 (magnetizing current / motor current) ]

Motor stator inductance

0.0

0.0

{mH}

2000 Will be automatically programmed by c48

(1)

Drive identification

• Indicates controller rating, format: xyz,

xy.z, x.yz, or x.y.z

• x. or x = voltage (2. = 200/240V, 1~;

2 = 200/240V, 3~; 4 = 400/480V, 3~)

• yz or y.z = kW rating

Examples:

2.0.3 = 200/240 V, 1~, 0.37 kW
47.5 = 400/480 V, 3~, 7.5 kW

User password

0

0

999

Changing from “0” (no password), value will
start at 763

When set to a value other than 0, must enter
password at C00 to access parameters

Software version

Display, format: x.yz

(1)

Changing these settings can adversely affect performance. Contact Lenze technical support prior to changing.