Installation

Typ

Installation gemäß EN 60204-1

Installation gemäß UL

FI-

Schutz-

schalter

2)

Sicherung

Sicherungs-

automat

L1, L2, L3, PE

[mm²]

Sicherung

(3)

L1, L2,
L3, PE

[AWG]

1/N/PE

ETMD371L2YXA, ETMD551L2YXA

M10 A

C10 A

1,5

10 A

14

> 30 mA

ETMD751L2YXA

M16 A

C16 A

2,5

15 A

14

ETMD112L2YXA

M20 A

C20 A

2,5

15 A

12

ETMD152L2YXA

M25 A

C25 A

2,5

20 A

12

ETMD222L2YXA

M30 A

C30 A

4,0

30 A

10

3/PE

ETMD371L2YXA...ETMD112L2_XA

(4)

M10 A

C10 A

1,5

10 A

14

ETMD152L2_XA

(4)

M16 A

C16 A

1,5

12 A

14

ETMD222L2_XA

(4)

M16 A

C16 A

2,5

15 A

12

ETMD402L2TXA

M25 A

C25 A

4,0

25 A

10

ETMD552L2TXA

M40 A

C40 A

6,0

35 A

8

ETMD752L2TXA

M50 A

C50 A

10

45 A

8

ETMD371L4TXA...ETMD222L4TXA

M10 A

C10 A

1,5

10 A

14

ETMD302L4TXA

M16 A

C16 A

1,5

12 A

14

ETMD402L4TXA

M16 A

C16 A

2,5

15 A

14

ETMD552L4TXA

M20 A

C20 A

2,5

20 A

12

ETMD752L4TXA

M25 A

C25 A

4,0

25 A

10

(1) Beachten Sie die geltenden örtlichen Vorschriften.
(2) FI-Schutzschalter für Impulsstrom oder Dauerstrom
(3) Schnelle Strombegrenzungssicherungen gemäß UL, Klasse CC oder T, 200.000 AIC erforderlich. Bussmann KTK-R, JJN, JJS, oder entspr.
(4) „_“ = Y oder T; die Bemessungsdaten sind für beide Modelle mit 3/PE-Eingang identisch.

EMV

Einhaltung von EN 61800-3/A11

Geräuschemission
Einhaltung der Grenzwerte Klasse A gemäß EN 55011 bei Installation in einem
Schaltschrank mit entsprechendem Unterbau-Filter und Motorleitungslängen unter 10
m.

A Abschirmungsklemmen

B Steuerleitung

C Motorleitung mit niedriger Kapazität

(Kern/Kern < 75 pF/m, Kern/Abschirmung < 150 pF/m)

D Elektrisch leitende Montageplatte

E Filter

Tmd005

B

C

D

A

E

3.2

Elektroinstallation

3.2.1 Installation gemäß EMV-Richtlinien

3.2.2 Sicherungen/Leitungsquerschnitte