12

ENGLISH

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze Selection

Password entry

0

0

999 Visible only when password is active

(see C94)

1

Setpoint and control
source

0

Setpoint source:

Control configuration:

0

Analog input (8U / 8I; see C34)

Control = terminals
Programming = keypad
Monitoring = LECOM

1

Code c40 / Code C47

2

Analog input (8U / 8I; see C34)

Control = terminals
Programming = LECOM / keypad
Monitoring = LECOM

3

LECOM

Control = LECOM
Programming = LECOM / keypad
Monitoring = LECOM

4

Analog input (8U / 8I; see C34)

Control = terminals
Programming = remote keypad
Monitoring = remote keypad

5

Code c40 / Code C47

6

Analog input (8U / 8I; see C34)

Control = remote keypad
Programming = remote keypad
Monitoring = remote keypad

7

Code c40 / Code C47

8

Analog input (8U / 8I; see C34)

Control = terminals
Programming = Modbus / keypad
Monitoring = Modbus

9

Code c40 / Code C47

10 Analog input (8U / 8I; see C34)

Control = Modbus
Programming = Modbus / keypad
Monitoring = Modbus

11 Code c40 / Code C47

Note

• When C01 = 1, 5, 7, 9, or 11 and C14 = 0...4, 6, 7, use c40 for speed setpoint
• When C01 = 1, 5, 7, 9, or 11 and C14 = 5, use C47 for torque setpoint
• When C01 = LECOM (3), write speed command to C46 or torque command to C47.

Load Lenze setting

0

No action/loading complete

• C02 = 1, 2, 3 only possible with

or

• C02 = 2 : C11, C15 and C89 = 60 Hz

and C87 = 1750RPM

1

Load 50 Hz Lenze settings

2

Load 60 Hz Lenze settings

3

Load OEM settings (if present)

WARNING!

C02 = 1...3 overwrites all settings! TRIP circuitry may be disabled!
Check codes CE1...CE4.

4.3

Parameter menu